The HVAC System is input as a ducted Gas Fired system with Cooling.  This type of system has a maximum fan power limitation of 0.45 w/cfm in cooling mode.

You can either change your system type to something other than a ducted Gas Furnace, or you must go to the System level of the Building Tree and in the HERS tab set this value to 0.45 w/cfm or less.